Tinsley Precision Instruments
Tinsley Precision Instruments

page location: home > products> air cooled shunts > type 2276

Air Cooled Shunts

Current Shunts Type 2276

The type 2276 range of high current shunts are specially designed for use up to 20,000 Amperes and maybe used on a steady D.C. load or for pulse work.

Limit of Error

Under steady condition the type 2276 shunts keep within 0.1% up to full rated current but this figure is greatly improved if forced air is used for cooling.

Stability

The stability of these shunts under steady conditions is 0.01% or better. A typical figure, 20000 Ampere shunt was found to be better than 0.005%.

Current Shunts Type 2276
 

Compensation for Phase Angle Errors

When used for pulse work, the mutual inductance between the potential leads and the current path in the shunt can be set to compensate for the phase angle between the current in the shunt and the voltage between the potential points.

The self inductance of the current through the shunt depends on the arrangement of the bus bars. If the return bus bar is made to follow the contours of the shunt and is kept close to it, the value can be kept to 0.01mH or less.

Construction

The construction of the type 2276 air cooled shunts is similar to the type 4638 but they are usually supplied in a steel lifting frame to facilitate transporting them without distortion. They are not supplied on a base nor fitted with a protecting cover.

For more information about this product contact Tinsley

 

Specifications

See the table below for a run-down of this product's specifications.

Current
Amperes

Resistance
Ohm

Volt Drop
Volts

Wattage
Watts

Dimensions
Millimetres (approx.)

4000
250
1
4W
2000 x 245 x 260
10000
10
0.1
1W
1200 x 330 x 330
20000
50
1.0
20W
2150 x 330 x 330

 

 

Hartest - Height of Precision