Transformer Test Equipment
Portable Transformer Ratiometer Model 4167F

Features
- Ratio range from 0.75 to 10,000:1
- Full automated measurement
- Features unique vector group detection
- Measuring voltage from 8V to 160V selectable or used from external source (8V .. 240V)
- Display shows ratio, phase angle, deviance and magnetising current
- Internal card reader supports handling parameter chip cards for saving all transformer specific measurement data.
- Easy to read LC display (256 x 128 pixel) with back light
- Special built in keyboard supports easy input of vectorgroup, phase measuring mode and parmeter
- RS232C port to get full external control over the instrument
- Centronics printer port
- Robust mobile case for field
For more information about this product contact Tinsley
|
The advantage of the 4167F is its simplicity to set-up.
Setting up the instrument is a simple case of typing in the vector group using the instrument front panel keypad and connecting to the offline transformer. All three phases are measured consecutively
with connecting and short circuit procedures at the primary and secondary voltage terminals performed automatically before each measurement. It is also possible to measure just one phase if required.
An adjustable set value permits the display of any error or deviation from the required transformation ratio. It is also possible for the 4167F to control the transformer tap changer and in this case all phases and taps are measured consecutively. Results can be stored internally using a transformer specific memory card, printed to an external printer or transferred to a PC via an RS232 interface.
By using a memory card, pre-programmed for a specific transformer type, the instrument can be made to show a PASS / FAIL message with the actual reading.
The transformer specific memory cards can be easily programmed via a personal computer using the built in card reader or by a cost efficient external card reader/writer directly connecting to a personal computer.
A market unique feature is the automatic vector group detection. If all connections to the transformer have been made, the correct vector group will be detected. In case of missing a connection (1N or 2N e.g.) there will be up to three possible vector groups displayed to the user. Once the correct vector group has been selected the instruments learns this and that group will be presented first next time.
The 4167F is connected to the H.V. and L.V. windings via four connections each. It also powers the transformer at a preset voltage supplied by an internal isolating transformer. However, external excitation using different voltages and frequencies is also possible. is its simplicity to set-up.
The 4167F is housed in a robust carrying case. All connections are provided at the front panel of the instrument and are locked in order to avoid accidental disconnection during a measurement. An alarm-warning lamp is also available and will illuminate whilst a measurement is in progress.
Technical Data
See the table below for a run-down of this product's technical data.
Ratio measurement
Range |
Range 0.75 – > 10,000 : 1 |
Max. errors (0,75 .. 2.500) |
± 0.1 % ± 1 d at 40 V .. 200 V
± 0.15% ± 1 d at 8 V .. 40 V |
Max. errors (2.500 .. 5.000) |
± 0.2 % ± 1 d at 40 V .. 200 V
± 0.3 % ± 1 d at 8 V .. 40 V |
Max. errors (5.000 .. 10.000) |
± 0.3 % ± 1 d at 80 V .. 200 V |
Max. errors (> 10.000) |
not specified (200 V) |
Measuring voltage |
8 V, 40 V, 80 V, 160 V selectable or by external source (8V .. 240 V) |
Measuring frequency |
45 Hz – 65 Hz (Line depended) |
Range selection |
full automatic |
Phase angle measurement
Range (one phase) |
- 9.9 ° to + 9.9 ° |
Range (three phase) |
- 179.9 ° to + 180 ° |
Max. error |
± 0.1 ° ± 2 digit |
Magnetising current measurement
Range |
1 mA – 2000 mA ± 1 % |
Multiplexer
Connections OS |
1U, 1V, 1W, 1N, (H0..H3) Amphenol |
Connections US |
2U, 2V, 2W, 2N, (X0..X3) Amphenol |
Connections ext. excitation |
8 V – 240 V AC, STASEI 5 |
Error detection
Contact-,Stability errors |
displays: HV/LV too low or too high, HV/LV interchanged and bad line stability |
Set point input |
using front keys, via RS232 or chip card |
Deviances |
shown on display, via RS232 |
Start of measurement |
using front panel, via RS232 |
Display |
256 x 128 pixel LC display, back light |
Result format |
vector group, actual phase, actual tap-position, ratio and deviation,
phase angle and deviation, exiting current, pass-fail result ref. to set point |
Measuring Time |
5 ... 20 s depending on line noise/distortion |
Measurement Storage |
200 sets of measurement data on chip card |
Correct Connection |
tested before each measurement |
Ports |
RS232C (full device control) printer (parallel, ANSI standard) |
Temperature |
Operating: 0° .. 50°C Storage: -5° ... 60°C |
Humidity |
0 ... 90% (Storage 95%) non condensing |
EMC, Safety, Vibration |
CE , IEC-1010-1 , ASTM D 999.75 |
Dimensions |
490 x 400 x 190 mm (WxDxH, mobile ABS rugged case) |
Weight |
approx. 12 kg without cables (mobile version) |
Accessories
- Warning light: The warning light shows if voltage appears on the test object during measurement.
- Cable HV 4pole, various lengths, amphenol jack and clamps (U, V, W, N)
- Cable LV 4pole, various lengths, amphenol jack and clamps (U, V, W, N)
- Calibration certificate
|
For more information about this product contact Tinsley
|